Description
Overview
The next-generation drive for heating, ventilation, air conditioning and refrigeration systems in commercial buildings. It adds HVACR-specific intelligence, more sensors and analytics, and hardware-based cybersecurity to protect the building management system. An ultra low-harmonic (ULH) variant is available for sites with sensitive grids or strict harmonic limits.
Technical Specifications:
Standard drives: 3 x 380-480 V AC: 1.1-710 kW
Ultra low-harmonic (ULH) drives: 3 x 380-480 V AC: 22-160 kW; THDi < 3-5%
Motor types: Induction (IM) and permanent-magnet (PM)
EMC: Built-in EMC filter, categories C1, C2, C3
Communication: Dual Ethernet or RS485; BACnet/IP, BACnet MS/TP, Modbus TCP, Modbus RTU, EtherNet/IP, PROFINET RT, EtherCAT
Functional safety: Safe Torque Off up to SIL3 / PL e as standard
Cooling: Back-channel cooling removes up to 90% of heat losses from the electrical room
Other features: Condition-based monitoring, sensor calibration, hardware-based cybersecurity
Key Benefits:
Clean power with the ULH variant meeting strict harmonic limits
Lower cooling costs thanks to back-channel cooling
Protected BMS with hardware-level cybersecurity
Maximum uptime through condition-based monitoring
Easy BMS integration with BACnet and Modbus built in
working process